Atallah, MMezouar, ABelgacem, Kh. saidi, . YBenmahdjoub, M.A2023-05-152023-05-152021-11-30Atallah, M. Mezouar,A. Belgacem, Kh. saidi, Y. Benmahdjoub ,M. A. Modeling and Power Control of 5th and 3rd order model for DFIG Applied of Wind Conversion System. International Journal of Energetica. Vo6. No 02.15/06/2021.faculty of technology. university of el oued. [visited in ../../….]. available from [copy the link here]2543-3717http://dspace.univ-eloued.dz/handle/123456789/22975ArticleIn this study, a comparison between the fifth-order model and the third-order model of the Doubly Fed Induction Generator (DFIG) is presented. This paper aims to study and analyze transient stability for the fifth-order and third-order models. The fifth-order model of the DFIG is based on five differentials equations. Neglecting the stator transients from the fifth-order model of the DFIG, we get the third-order. On startup and control of the power system that the third-order model produces better results than the fifth-order model in the transient regime. The performance of the two models on the startup and control of the power system is proved with the simulations (MATLAB/Simulink® software).enDFIG, Transient stability, Wind energy, Vector controlModeling and Power Control of 5th and 3rd order model for DFIG Applied of Wind Conversion SystemArticle